What kind of oil do you use with 407C?

Editorial team Published on

You need to use Polyolester (POE) oil with R-407C.

Does 407C require an oil change?

R-407C is entirely immiscible with mineral oil, so a complete oil change to POE will be necessary when retrofitting an R-22 installation. After changing the oil, it pairs well with R22. If you prefer not to change the oil, M099 is a suitable alternative, though you might experience up to a 10% reduction in capacity.

Do you charge 407C as a liquid?

Yes, R-407C must always be charged into the system as a liquid. Because it is a zeotropic blend of three different refrigerants (HFC-32, HFC-125, and HFC-134a), charging it as a vapor will cause the blend to separate (fractionation), ruining the ratio of the mixture and altering the system's performance.

Can R-407C be used with mineral oil?

No, R-407C is not compatible with mineral oil.

Can I use 407C with POE oil?

POE lubricant is recommended for use with Freon™ 407C. In order to achieve equivalent miscibility to R-22/oil, the residual oil should be about 5 wt% or less of the total lubricant used in the system. In larger systems, this amount of residual mineral oil can be achieved by using a flushing technique.

Adding POE Oil for and R407c Retrofit

What oil is compatible with R-407C?

R-407C is primarily compatible with Polyolester (POE) oil. While R-22 systems often use Mineral Oil (MO) or Alkylbenzene (AB), R-407C requires POE to ensure proper miscibility and oil return to the compressor. When retrofitting an R-22 system, the oil must be changed to POE, with recommended residual MO levels below 5%.

What happens if I add too much PAG oil to an AC system?

Putting too much PAG oil in an A/C compressor leads to a phenomenon called oil overcharge, which compromises both cooling performance and hardware integrity. An excess of oil coats the inside of A/C lines, displacing refrigerant and creating a variety of system-level issues.

What are the common issues with R-407C?

The general observed trend was a drop in both capacity and efficiency and also in suction and discharge pressures. It was due to a loss ofR32 which is the highest pressure component in the mixture. Flammability issue may have to be considered for vapor leaks due to the higher percentage of R32 in the leaking vapor.

Is 407C being phased out?

Yes, R-407C is being phased out. Under the US EPA AIM Act, production and use of high-Global Warming Potential (GWP) refrigerants, including R-407C, are strictly restricted.

Can you dump 407C on top of R-22?

R22 uses mineral oil. R407C requires POE oil. Mixing them prevents oil circulation, starves the compressor, and causes mechanical failures.

What is the refrigerant oil in R-407C?

R407C refrigerant requires Polyolester (POE) oil for system lubrication. POE oil is miscible with R407C, meaning it mixes well and circulates through the system to return to the compressor, whereas standard mineral oil (used with older refrigerants like R-22) will cause sludge and compressor failure.

What pressure does 407C run at?

R-407C operating pressures depend heavily on the ambient temperature. Generally, the suction (low side) pressure runs between 50 to 80 psig, while the discharge (high side) pressure runs between 240 to 320 psig in typical AC operation.

Which refrigerant can replace R-407C?

Opteon™ XP20 (R-449C) refrigerant is a hydrofluoroolefin (HFO) option that replaces R-22 and R-407C in residential and commercial air conditioners, as well as direct expansion chillers. It has similar performance and properties to R-22 and R-407C and can be used in both retrofit and new equipment.

Is R-407C a good refrigerant?

R407C is an efficient and well-proven refrigerant that performs well in air conditioning and heat pump systems. Its biggest advantage is its similarity to R22, making it a convenient replacement in retrofits. However, due to its high GWP, it requires responsible use and compliance with environmental regulations.

Can you replace R-407C with R410A?

R407C won't work with R410A as the discharge pressure, power consumption is also not the same. The popular recommended Freon that is compatible with R410A is R-32 and it has significantly less amount of GWP than R410A. For R407C, R134A, R125, and R32 are compatible and can go together in the natural environment.

How should 407C be charged?

To avoid fractionation, R-407C should be removed from the cylinder as a liquid, and charged into the suction line during equipment operation. This can be done with a liquid charging adapter, which causes the liquid refrigerant to flash to a vapor prior to entering the system.

Does 407C use the same oil as R22?

R407C requires synthetic polyolester (POE) oil rather than the mineral oil used in many older R22 systems. This means converting to R407C often involves a complete oil change and flushing of the system to remove all traces of mineral oil.

What AC gas is now illegal?

As of January 1, 2020, the United States banned the use of the R22 refrigerant, commonly known as Freon.

How much is 30 lbs of R22 worth?

A 30-pound cylinder of R-22 refrigerant is generally worth between $500 and $1,200 to purchase wholesale, and up to $2,400 to $4,500 if bought directly from a service company during a home repair.

Do you need a license to buy 407C?

You need at least Type II or Universal certification to buy or handle most HVAC refrigerants such as R410A, R407C, R22, etc.

How much is a pound of R-22 right now?

R-22 refrigerant typically costs between $𝟗𝟎 and $𝟐𝟓𝟎 per pound. Because R-22 has been phased out, the supply is dwindling, which causes prices to continuously climb.

What is the new refrigerant coming out in 2026?

A2L refrigerants, the new refrigerants for 2026, will replace R-410A in new systems. A lot about A2L refrigerants is explained in their name: The “A” means low toxicity. The “2L” is a safety classification, indicating it is mildly flammable.

What type of oil does 407C use?

The lubricant that is currently used with R-22 is either Mineral Oil (MO) or Alkylbenzene (AB). The retrofit procedure to R-407C, recommended by manufacturers, requires a lubricant change to Polyol Ester (POE) since the solubility and miscibility of R-407C in either MO or AB are much lower than in POE.

Can 407C be used as a drop-in for R22?

While R-407C is the closest match to R-22 in terms of pressures and cooling capacity, it is not a true "drop-in" replacement. You cannot simply pour it into an existing R-22 system without professional modifications and a full evacuation.

What is the normal pressure for R407C?

For an R-407C air conditioning or refrigeration system running under normal conditions (around 80°F to 95°F ambient temperature), expect a suction pressure of 70 to 85 psig and a discharge pressure of 200 to 260 psig.

← Previous article
How do I know what kind of smoke detector I have?
Next article →
How abrasive is Magic Eraser?