What is the height of a fire alarm box?

Author: Emile Runolfsdottir  |  Last update: Friday, June 13, 2025

2.2 - Height (42 - 48 inches) The height of the manual fire alarm boxes shall be not less than 42 inches and not more than 48 inches measured vertically, from the floor level to the activating handle or lever of the box. 2013 NFPA 72 17.14.

What is the height of a fire alarm panel?

A4.2.3.

Fire alarm panels (standard Kentec) with LCD display should be mounted such that the top of the panel is at 1.65 metres +/- 0.1 metres above floor level.

What is the height of a fire department Knox box?

The Knox Box must be mounted on the exterior of a structure at a height of five (5) feet from the ground to the bottom of the box. The Knox Box must be mounted in a location that is clear of natural and man-made obstructions.

What is the height code for fire alarms?

What is the required height for a fire alarm pull station? The simple answer that the operable part of the pull station needs to be at least 42 in. (1.07 m), and not more than 48 in. (1.22 m), above the finished floor.

What is the height of a fire alarm pull station?

What height should a fire alarm pull station be installed? All fire alarm pull stations need to be installed anywhere from 42 to 48 inches from the floor.

What is a Fire Alarm System?

How high should a fire alarm box be?

2.2 - Height (42 - 48 inches) The height of the manual fire alarm boxes shall be not less than 42 inches and not more than 48 inches measured vertically, from the floor level to the activating handle or lever of the box.

How high should fire alarm wall be?

Wall-mounted alarms should be installed not more than 12 inches away from the ceiling (to the top of the alarm). If you have ceilings that are pitched, install the alarm within 3 feet of the peak but not within the apex of the peak (four inches down from the peak).

What is the ADA height for a fire alarm pull station?

Requirements for Fire Alarm Systems

The pull lever cannot require tight grasping, pinching, or twisting of the wrist. In addition, the pull lever should be within reach range or between 48 inches and 15 inches above the finish floor or ground.

Where to install a pull station?

NFPA 72 requires a pull station within 60 inches of every individual exit, and for groups of doors that are more than 40 feet wide away from each other, there must be a pull station on both sides of the grouping. The placement of fire alarm pull stations is critical to ensuring they provide the protection intended.

What is the mounting height for the Knox Box 3200?

Suggested minimum mounting height, 6 feet above ground. ATTENTION: KnoxBox is a very strong device that MUST be mounted properly to ensure maximum security and resist physical attack.

What is the standard height for fire block?

Unfaced fiberglass batt insulation used as fireblocking shall fill the entire cross section of the wall cavity to a minimum height of 16 inches (406 mm) measured vertically.

What is the height of fire equipment?

To prevent fire extinguishers from being moved or damaged, they should be mounted on brackets or in wall cabinets with the carrying handle placed 3-1/2 to 5 feet above the floor. Larger fire extinguishers need to be mounted at lower heights with the carrying handle about 3 feet from the floor.

Where should a fire alarm panel be located?

Preferably in an area of low fire risk and on the ground floor by the entrance used by the Fire Brigade and preferably viewable from outside of the building. It should be located in an area common to all building users and where automatic detection is in use, the Control Panel should be in a protected area.

What is the standard height of an alarm keypad?

The standard height for an alarm system keypad is probably around 4.5 feet high. However, anywhere from 4 to 5 feet up is usually okay.

What is the clearance for a fire alarm panel?

A minimum of 36-inches clearance in front of the panel must be maintained from the floor to 6-feet, 6-inches above the panel, or to the top of the panel whichever is highest. A minimum of 30-inches clearance from side to side must be maintained in front of the panel.

What is the standard height of a fire alarm panel?

NFPA 72 sets standards for the minimum and maximum mounting heights for fire alarm control units. The devices must be located between 1.5 and 5.5 feet above the finished floor to provide maximum accessibility.

What is the mounting height of a manual fire alarm box?

The height of the manual fire alarm boxes shall be not less than 42 inches (1067 mm) and not more than 48 inches (1372 mm) measured vertically, from the floor level to the activating handle or lever of the box.

What is the height code for a fire alarm?

The NFPA 72 or the National Fire Alarm and Signaling Code requires the manually operable part of the fire alarm system to be installed at a minimum height of 42 inches (1.07 m). The pull station height should not be more than 48 inches (1.22 m) from the finished floor.

What height should a fire alarm sounder be mounted?

How high should I mount a sounder/beacon? A standard sounder/strobe or individual strobe should be mounted 2.1m above the floor and not closer than 150mm from the finished ceiling.

What are the NFPA 72 requirements?

A: Some of the key requirements of NFPA 72, National Fire Alarm and Signaling Code include: providing fire alarm systems that are designed, installed, inspected, tested, and maintained to meet the code's standards, providing fire alarm control units that are designed and installed to detect fires and initiate an alarm ...

What height should a fire alarm repeater panel be mounted?

The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level position such that the enclosure is not distorted.

What is the height of a pull station?

According to NFPA 72, each pull station must be installed between 42 and 48 inches from the floor to ensure easy accessibility for people in wheelchairs. In addition, it needs to be placed in a location that's from free obstacles. This way any individual may access the pull station in the event of an emergency.

How high should a pull-up be?

Your head is about 1 foot high. Given room for additional motion, this means you should mount your pull-up bar a minimum of 18 inches below the ceiling where your head will be while performing pull-ups.

What is the ADA height for a pull station?

If the path to the ADA-compliant fire extinguisher or pull station is unobstructed, the operable part must be placed from 15 inches to 48 inches off of the finished floor or ground. But when the wheelchair user must reach over an obstruction, these heights may change.