Can a Type B vent run horizontal?

Author: Mr. Alan Wunsch  |  Last update: Sunday, January 11, 2026

B-Vent is intended for neutral or negative draft applications. It is designed for vertical installations (including laterals) but may be used for horizontal applications with a draft-inducing fan located such that all indoor portions of the vent are under negative pressure.

Can b vent be used horizontally?

No. Per the sizing tables, all orientations must terminate vertically with a UL listed rain cap, otherwise the appliance may not vent properly.

Can you run a vent pipe horizontally?

While you can indeed run a horizontal vent pipe, you can't do it indefinitely; this is designed to provide your pipes with the ability to drain into the sewer system. The typical rule of thumb according to code requires you to run a horizontal pipe for no more than one-third of the total length.

What is the code for a horizontal vent?

905.3. 1 Horizontal Vent

A horizontal vent that is less than six inches in height above the flood level rim of the fixture being served must be served with a clean out.

What is the minimum slope required for a type B vent installed horizontally?

Maintain a pitch or rise from the appliance to the vent cap on horizontal runs. The pitch shall not be less than ¼ inch to the foot.

Gas Venting: Part 1 - Code Requirements for Vents and Chimneys

What are the requirements for a type B vent?

Type B vents must be equipped with their own special chimney caps. If the cap is damaged or lost, it should not be substituted with something not recommended by the manufacturer. The clearance required from combustible materials is printed on the flue's exterior metal surface, and is generally 1 or 2 inches.

How long can a 2 vent run horizontal?

If you have 1 ¼-inch pipe, the horizontal distance of the vent should not be more than 30 inches. For a 1 ½-inc pipe the vent should be 42 inches away at the most while a 2-inch pipe must have a maximum distance of 5 feet.

What is the minimum clearance required between a Type B vent and a horizontal or vertical window?

Appliances designed for natural draft venting and incorporating integral venting means shall be located so that a minimum clearance of 9 inches (229 mm) is maintained between vent terminals and from any openings through which combustion products enter the building.

How much of a vents total permitted length may be run on the horizontal?

Not to exceed one-third of the total permitted length of a vent shall be permitted to be installed in a horizontal position.

Which Type B vents shall not be used for venting?

Type B Vent shall not be used to vent flue products from incinerators, combination gas/ oil appliances, oil-fired, or wood-burning appliances. If there is a question about the use of Type B Vents, contact the appliance manufacturer or DuraVent's Engineering Department for further information. 1. Appliances.

How much slope is needed on a horizontal vent pipe?

The slope of the vent section of the horizontal branch drain shall be not greater than 1 unit vertical in 12 units horizontal (8-percent slope).

Can a studor vent be installed horizontally?

STUDOR AAVs must be installed in the vertical, upright position. A maximum deviation (in either direction) of 15 degrees is allowed. The vent shall connect to the drain vertically to maintain an unobstructed opening in the piping to the STUDOR AAVs.

Does a vent pipe have to be vertical?

Vent pipes must be installed so they stay dry. This means that they should emerge from the top of the drainpipe, either straight vertically or at no less than a 45-degree angle from horizontal, so that water cannot back up into them.

Why use Type B vent?

Type B Gas Vent Systems Give You These Important Advantages

Safety of the Hart & Cooley® system is assured by the double-wall, air-insulated design and locking joints. Properly installed, the vent cannot come apart through vibration, and offers protection against vent failure or fire hazard.

What category is Type B vent?

B-vent is ONLY allowed on Category 1 appliances unless the appliance manufacturer has specifically certified a particular B-vent system to be used alternatively.

Can you run B vent through a wall?

Gas Vent Connectors

Double-wall corrugated aluminum with B vent ends can be used anywhere B vent is used, except where it passes through walls, floors, ceilings, and inside enclosures.

How far can you run B vent horizontally?

The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems.

How many toilets are on a 3 inch horizontal drain?

No more than four water closets or bathroom groups shall be installed on a 3" horizontal fixture branch. EXCEPTION: Where the water closets are rated 3.5 gallons or more per flush, no more than two water closets or bathroom groups shall be permitted.

What is the clearance code for B vent?

THE MINIMUM CLEARANCE OF 1 INCH FROM THE VENT PIPE SURFACE. In multi-story buildings, a firestop must be provided at every point where the vent p asses through a floor or ceiling.

How close can drywall be to B vent?

Drywall and wallboard are considered combustible materials and should not be installed against the vent including the use of this material to close off the hole around the vent. Type B Gas Vent requires a minimum of one-inch clearance to combustibles.

Does a B vent need to be sealed?

All unused openings in a gas vent must be sealed to prevent loss of effective vent action. Firestop Spacer/ Support Plate Firestop Spacer placed on top of floor or framed opening. and maintained. All Type B Gas Vents passing through floors, ceilings or walls must be firestopped using the Firestop Spacer as per Fig.

Why do horizontal vents need a slight grade to them?

Check the slope of the B-vent pipe: The pipe should be installed with an upward slope of at least 1/4 inch per foot to ensure that developing condensate and flue gases can flow through the pipe. If the pipe isn't sloped correctly, it may cause air to become trapped and block airflow.

How long can a horizontal flue be?

As a general rule, a flue should work effectively when it's up to 10 metres in length. This is usually based on a standard thickness of 60/100mm. For flues that need to be longer than this, it's a good idea to increase the thickness to 80/125mm to ensure that the gases are able to escape easily.

Previous article
Is it better to flush or throw away toilet paper?
Next article
How to recognize when a roof is about to collapse?