No. Per the sizing tables, all orientations must terminate vertically with a UL listed rain cap, otherwise the appliance may not vent properly.
While you can indeed run a horizontal vent pipe, you can't do it indefinitely; this is designed to provide your pipes with the ability to drain into the sewer system. The typical rule of thumb according to code requires you to run a horizontal pipe for no more than one-third of the total length.
905.3. 1 Horizontal Vent
 A horizontal vent that is less than six inches in height above the flood level rim of the fixture being served must be served with a clean out.
Gas Vent Connectors
 Double-wall corrugated aluminum with B vent ends can be used anywhere B vent is used, except where it passes through walls, floors, ceilings, and inside enclosures.
Vent pipes must be installed so they stay dry. This means that they should emerge from the top of the drainpipe, either straight vertically or at no less than a 45-degree angle from horizontal, so that water cannot back up into them.
No. Sure-Vent must be installed as close to vertical as possible. You cannot have the Sure-Vent tilted more than 15° from side to side, otherwise it will not operate properly.
Remember How Air Flows
 If it's hot outside and your vents are located near the floor, then you should adjust the vents so that the cold air will flow upward. If it's cold outside and your vents are located near the ceiling, then you need to point the vents downward.
The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent except for engineered systems. The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems.
Type B Gas Vent requires a minimum of one-inch clearance to combustibles. This one-inch is a typical clearance for all brands of Type B Vent, but each section of vent pipe is marked with the clearance required by Underwriter Laboratories, so it should be checked.
Type B vents must be equipped with their own special chimney caps. If the cap is damaged or lost, it should not be substituted with something not recommended by the manufacturer. The clearance required from combustible materials is printed on the flue's exterior metal surface, and is generally 1 or 2 inches.
Type B Vent shall not be used to vent flue products from incinerators, combination gas/ oil appliances, oil-fired, or wood-burning appliances. If there is a question about the use of Type B Vents, contact the appliance manufacturer or DuraVent's Engineering Department for further information. 1. Appliances.
Maintain a pitch or rise from the appliance to the vent cap on horizontal runs. The pitch shall not be less than ¼ inch to the foot.
Check the slope of the B-vent pipe: The pipe should be installed with an upward slope of at least 1/4 inch per foot to ensure that developing condensate and flue gases can flow through the pipe. If the pipe isn't sloped correctly, it may cause air to become trapped and block airflow.
Appliances designed for natural draft venting and incorporating integral venting means shall be located so that a minimum clearance of 9 inches (229 mm) is maintained between vent terminals and from any openings through which combustion products enter the building.
A plumbing vent does not necessarily have to go straight up. While it is common for vents to run vertically and extend through the roof, there are alternative venting methods available, including: Horizontal vents: These vents run parallel to the building's floor and connect to a vertical vent or vent stack.
Both the combustion air and vent pipes must attach to the vent kit. The vent kit must terminate outside of the structure and should be installed vertically as shown in Figures 3 and 4, or horizontal as shown in Figures 5 and 6.
THE MINIMUM CLEARANCE OF 1 INCH FROM THE VENT PIPE SURFACE. In multi-story buildings, a firestop must be provided at every point where the vent p asses through a floor or ceiling.
Type B Gas Vent has been engineered to heat up rapidly. It remains hot during the operation of the appliance with minimal condensation in the appliance and vent system.
Yes. Because this is a B-vent, it has zero-clearance to combustibles. We do recommend using 1/2” cement board beneath the unit when building on a wood subfloor.
Direct vent is much more efficient, you're pulling fresh air from outside of the house. While you're simultaneously exhausting and gives you more flexibility from an install stand point and most of all direct vent systems are going to heat much better because they are sealed units.
They are not needed to secure a connection because the connection is already UL listed as it is designed. However, there are exceptions that we allow screws and that is for connections of single-wall pipe to the B-vent.
A horizontal flue, coming out of an external wall, is most commonly used in the UK as it is usually the most direct route from the boiler to the outside.
Placing the heat vents beneath the windows is actually best for efficiency and proper airflow. Essentially, you want to target your warm air where the home is cold. If you'd placed heat vents in your ceiling, for example, then this part of the home would get hot, neglecting to heat up the sides of the home as much.
The Difference Between Return and Supply Vents
 To change the direction of the grates, you have to unscrew the entire grille and turn it upside down. On the other hand, supply vents usually have a small lever that allows you to adjust the direction of the grates so air can blow at or away from a specific area.
While living in the south, you may have noticed that extreme heat is more common than extreme cold. If you remember basic science, you'll know that hot air rises, and cold air sinks, making ceiling vents the delivery location of choice for places that often experience warmth and humidity.