Can b vent be used horizontally?

Author: Dr. Rhiannon Rowe  |  Last update: Monday, January 12, 2026

B-Vent is intended for neutral or negative draft applications. It is designed for vertical installations (including laterals) but may be used for horizontal applications with a draft-inducing fan located such that all indoor portions of the vent are under negative pressure.

How far can you run B vent horizontally?

The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems.

Can you run a vent pipe horizontal?

While you can indeed run a horizontal vent pipe, you can't do it indefinitely; this is designed to provide your pipes with the ability to drain into the sewer system. The typical rule of thumb according to code requires you to run a horizontal pipe for no more than one-third of the total length.

Can you run B vent through a wall?

Gas Vent Connectors

Double-wall corrugated aluminum with B vent ends can be used anywhere B vent is used, except where it passes through walls, floors, ceilings, and inside enclosures.

Can you vent a unit heater horizontally?

On horizontal vent runs, the flue pipe must be pitched down toward the terminal end—1/4-inch per foot for condensate drainage—for the entire length of the horizontal vent run . Failure to pitch the vent run properly may damage the heater due to condensate running back into the unit .

Gas Venting: Part 1 - Code Requirements for Vents and Chimneys

What is the difference between vertical and horizontal venting?

Horizontal vents are installed along the length of a drainpipe and are typically used in homes with long, straight drainpipes. They are less expensive to install than vertical vents, but they can be more difficult to clean. Vertical vents are installed near the top of a drainpipe and extend up through the roof.

How much of a vents total permitted length may be run on the horizontal?

Not to exceed one-third of the total permitted length of a vent shall be permitted to be installed in a horizontal position.

What are the requirements for a type B vent?

Type B vents must be equipped with their own special chimney caps. If the cap is damaged or lost, it should not be substituted with something not recommended by the manufacturer. The clearance required from combustible materials is printed on the flue's exterior metal surface, and is generally 1 or 2 inches.

Can drywall touch a B-vent?

Type B Gas Vent requires a minimum of one-inch clearance to combustibles. This one-inch is a typical clearance for all brands of Type B Vent, but each section of vent pipe is marked with the clearance required by Underwriter Laboratories, so it should be checked.

What is the minimum slope required for a Type B vent installed horizontally?

Maintain a pitch or rise from the appliance to the vent cap on horizontal runs. The pitch shall not be less than ¼ inch to the foot.

Does a vent have to be vertical?

Vent pipes must be installed so they stay dry. This means that they should emerge from the top of the drainpipe, either straight vertically or at no less than a 45-degree angle from horizontal, so that water cannot back up into them.

How long can a 2 vent run horizontal?

If you have 1 ¼-inch pipe, the horizontal distance of the vent should not be more than 30 inches. For a 1 ½-inc pipe the vent should be 42 inches away at the most while a 2-inch pipe must have a maximum distance of 5 feet.

What is the minimum clearance required between a Type B vent and a horizontal or vertical window?

Appliances designed for natural draft venting and incorporating integral venting means shall be located so that a minimum clearance of 9 inches (229 mm) is maintained between vent terminals and from any openings through which combustion products enter the building.

What is the clearance code for B vent?

A 1-inch clearance (air space) to combustible materials must be maintained, when using DuraVent Round B-Vent, regardless of the pipe diameter. at least 2 feet higher than an adjacent wall or obstruction, if it is within 8 feet.

Does a plumbing vent have to go straight up?

A plumbing vent does not necessarily have to go straight up. While it is common for vents to run vertically and extend through the roof, there are alternative venting methods available, including: Horizontal vents: These vents run parallel to the building's floor and connect to a vertical vent or vent stack.

How long can a horizontal flue pipe be?

There is currently no maximum or minimum length specified in the building regs. They do say that single skin flue pipe mustn't pass through any roof space, floor or internal wall.

How much clearance is needed for a B vent pipe?

Selkirk Type B Gas Vents 3 through 24 inch sizes must be installed with ONE INCH MINIMUM AIR SPACE CLEARANCE TO COMBUSTIBLES! 26 through 48 inch sizes require TWO INCHES MINIMUM AIR SPACE CLEARANCE TO COMBUSTIBLES. These clearances are marked on all gas carrying items.

Does b vent get hot?

Type B Gas Vent has been engineered to heat up rapidly. It remains hot during the operation of the appliance with minimal condensation in the appliance and vent system.

Can you put a cheater vent in the wall?

Don't confuse AAVs with smaller and cheaper mechanical vents. Sometimes called "cheaters," these tubular, spring-loaded $5 vents are rated for only 1/2 DFU (drainage fixture unit), and are not allowed under most building codes.

When shall Type B vents only be used?

Type B gas vents may be used to vent gas appliances listed for use with Type B gas vent. Hart & Cooley Type B vents are not to be used with appliances burning solid or liquid fuels.

Which is better direct vent or B vent?

Direct vent is much more efficient, you're pulling fresh air from outside of the house. While you're simultaneously exhausting and gives you more flexibility from an install stand point and most of all direct vent systems are going to heat much better because they are sealed units.

How far does B vent need to be above the roof?

For example, a 6-inch (152 mm) diameter Type B vent must extend above a simple gabled roof only 1 foot (305 mm) for roofs having up to 6/12 pitch, if the terminal is not within 8 feet (2438 mm) of a vertical surface such as an upper-story exterior wall.

What is the code for venting a toilet?

It's typically recommended that you go with a 2" PVC pipe for the vent. This is according to the uniform plumbing code (UPC). It may not be enough, depending on how many fixtures you are trying to run off the vent. You should check with local building code requirements to be on the safe side.

How many toilets are on a 3 inch horizontal drain?

No more than four water closets or bathroom groups shall be installed on a 3" horizontal fixture branch. EXCEPTION: Where the water closets are rated 3.5 gallons or more per flush, no more than two water closets or bathroom groups shall be permitted.

Previous article
Is cold air bad for wood?
Next article
What is the best thing to run through a washing machine to clean it?