What are the three main considerations that determine the required standpipe system installation?

Author: Mr. Manuela Weber PhD  |  Last update: Monday, April 21, 2025

What are the three main considerations that determine the required standpipe system installation? The building height above or below the level of fire department access, whether a fire sprinkler system is installed, the use and occupancy of the building.

What are the requirements for a standpipe in construction?

(2) Every building six (6) stories or more in height shall be provided with not less than one operable standpipe. Such standpipes shall be installed when the progress of construction is not more than 50 feet in height above grade.

What are the three types of standpipe systems?

Standpipes have three major classifications:
  • Class I standpipes serve a 2.5-inch fire hose connection for fire department use. ...
  • Class II standpipes serve a 1.5-inch fire hose connection and are typically found in cabinets. ...
  • Class III standpipes have both connections of Class I and II.

What NFPa standard establishes the design and installation requirements for standpipe systems?

NFPA 14 provides requirements for the installation of standpipes and hose systems to ensure that systems will work as intended to deliver adequate and reliable water supplies in a fire emergency.

Which of the following standpipe system considerations are critical for inspectors to verify during inspections?

As an inspector utilizing NFPA 1, Fire Code, you need to know three things about standpipes when determining if a building and system is compliant with the Code: (1) Where are standpipes required, (2) What type of system is required and (3) Has the system been properly inspected, tested, and maintained.

Firefighting Lesson 1 | Sizing the pump for standpipe and fire hose system

What NFPA standards are needed for standpipes?

NFPA 14 Standpipe Requirements

Hydraulic Calculations: Systems must be designed to ensure adequate water flow and pressure. NFPA 14 provides detailed requirements for calculations. Pipe Sizes and Materials: Standpipes must be constructed from materials capable of handling high pressure and water flow.

What determines the pressure requirements for pumping to a standpipe system?

It takes into account factors such as pipe length, pipe diameter, and friction loss. By using the CPM, engineers can determine the discharge pressure needed to pump water through the standpipe system. The Hazen-Williams Formula is another method used to determine the discharge pressure for fire pumping operations.

What are the requirements for a Class 1 standpipe system?

The minimum residual pressure required for a Class I system is 100 psi (6.9 bar) from the hydraulically most remote 2 ½ in. (65 mm) hose connection with a flow rate of 500 gpm (1893 L/min), through the two most remote 2 ½ in. (65 mm) hose connections.

What are the requirements for standpipe drains?

The trap and fixture drain for an automatic clothes washer standpipe shall be not less than 2 inches (51 mm) in diameter. The fixture drain for the standpipe serving an auto- matic clothes washer shall connect to a 3-inch (76 mm) or larger diameter fixture branch or stack.

Which NFPA standard deals with the installation of sprinkler systems?

Standard for the Installation of Sprinkler Systems

The industry benchmark for design and installation of automatic fire sprinkler systems, NFPA 13 addresses sprinkler system design approaches, system installation, and component options to prevent fire deaths and property loss.

What is the total flow required for a standpipe system with 3 standpipes in a building constructed without fire sprinklers?

Minimum flow for additional standpipes shall be 250 gpm per standpipe for floor areas less than or equal to 80,000 square feet. For a building with at least 80,000 square feet per floor, 500 gpm is required for the second standpipe and 250 gpm for the third standpipe, if required for a nonsprinklered building.

What is considered a standpipe?

A standpipe or riser is a type of rigid water piping which is built into multi-story buildings in a vertical position, or into bridges in a horizontal position, to which fire hoses can be connected, allowing manual application of water to the fire.

What PSI should a standpipe system be?

The minimum pressure while flowing the required standpipe flow (500 GPM from the hydraulically most remote standpipe and 250 GPM from each additional standpipe, up to a maximum of 1000 GPM for a fully sprinklered building) shall be 100 psi at any valve outlet while flowing 250 GPM through each valve.

What are the three classes of standpipe systems?

Class I systems are designed for use by fire departments with 2½” hose connections. Class II systems are designed for use by trained personnel or fire departments with 1½” hose connections. Class III systems are designed for use by trained personnel or fire departments with both 1½” and 2½” hose connections.

What is the current NFPa 13?

The Fire Sprinkler Code, 2022 (NFPA 13, 2022) is a code produced by the National Fire Protection Association (NFPA). This document provides the foundation for many state and city codes. The NFPA 13, 2022 combined with local jurisdiction amendments form the state codes.

What are three types of pressure regulating devices?

There are three common types of pressure-regulating devices, including pressure-restricting valves, pressure-reducing valves and pressure-relief valves. Each valve type has different uses and means of operation.

What procedures require drains?

Surgeons use them to drain fluid after several procedures, like:
  • Abdominal surgery, including hernia repair surgery.
  • Breast surgery, including breast cancer surgery and top surgery.
  • Chest surgery, including procedures to remove fluid buildup in your chest, like pleural effusion.

Where do most codes require the FDC to be placed?

FDCs are typically located on the outside of the property they protect, but can sometimes be completely separated from the building altogether. Such FDCs are known as freestanding or sidewalk FDCs. In any case, NFPA 13 requires FDCs to be located on the street side of the property (if possible).

Is a standpipe required in an existing building?

Class I standpipes shall be installed in existing buildings with occupied floors located more than 50 feet (15 240 mm) above or below the lowest level of fire department vehicle access.

Who can use a standpipe?

We allow licensed commercial customers to remove water from standpipes for building, road cleaning, graffiti removal or landscaping work. To use a standpipe on our network, you must have a licence, and hire a metered standpipe from our service provider, Aquam.

Where are Class 1 standpipes located?

[F] 905.4 Location of Class I Standpipe Hose Connections

In every required interior exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at the main floor landing unless otherwise approved by the fire code official.

What is a class 3 fire hose cabinet?

Class III Systems shall provide [1-1/2″ (38 mm)] hose stations to supply water for use by trained building occupants and [2-1/2″ (64 mm)] hose connections to supply a larger volume of water for use by fire departments and those trained in handling heavy water streams.

What determines pressure in a pipe?

This overall pressure difference across the pipe is related to a number of factors: Friction between the fluid and the wall of the pipe. Friction between adjacent layers of the fluid itself. Friction loss as the fluid passes through any pipe fittings, bends, valves, or components.

What tests should be performed on a standpipe system after its installation is complete?

Pressure test for hoses after 5 years of installation, and every 3 years after the initial 5 year period. A comprehensive backflow preventer test. Control valves and pressure-reducing valves. A full system flow test.

What is the standpipe test?

The standpipe test is one of the simplest tests for measuring the water absorption characteristics of concrete. A vertical tube is bonded onto the horizontal concrete surface to be tested. The tube is then filled up with water to a certain level and then allowed to be absorbed into the concrete.

Previous article
Is condensation worse in unheated homes?
Next article
Is filtered water clean enough to drink?