How far should a smoke detector be from the AC unit?

Author: Darian Mueller PhD  |  Last update: Thursday, June 12, 2025

Smoke alarms and smoke detectors shall not be installed within a 36-inch (910 mm) horizontal path from the supply registers of a forced air heating or cooling system and shall be installed outside of the direct airflow from those registers.

How far should a smoke detector be from AC?

Guideline. The guideline in this case is that you shouldn't put alarms within 400mm of air conditioning vents or the blades of a ceiling fan, however we recommend 1m if possible.

How close can a smoke detector be to an AC vent?

- Within 3 feet of an air supply vent (supply or air flow) - Within 1 foot of a light fixture. - Within the “dead air space” where the wall meets the ceiling (ceiling smoke alarms must be at least 4” from the wall, wall mounted smoke alarms must be at least 4” and no more than 12” from the ceiling.

Where should smoke detectors be placed in HVAC?

Annex A, A. 17.7. 4, recommends that detectors not be located in the direct airflow or closer than 36 inches from air supply diffuser or return air opening. This recommendation is intended to prevent airflow from diluting smoke or delaying smoke reaching the detector, both of which can significantly delay detection.

What are the requirements for a smoke detector in HVAC?

The International Mechanical Code requires a duct smoke detector in the return for units over 2000 cfm and requires a detector in the supply duct for systems over 15,000 cfm.

National Electrical Code - Smoke Detectors

Where should smoke alarms not be placed?

Avoid near fresh air vents, ceiling fans or very drafty areas (drafts can blow the smoke away from the detector/alarm). Avoid installing closer than 4 inches from the wall or corners.

Are duct smoke detectors designed to detect smoke in HVAC ductwork?

Duct smoke detectors provide early detection of smoke and products of combustion present in air moving through HVAC ducts. These devices are designed for prevention of smoke recirculation in areas by the air handling systems. Fans, blowers and complete systems may be shut down in the event of smoke detection.

What is the code for smoke detector locations?

For many years NFPA 72, National Fire Alarm and Signaling Code, has required as a minimum that smoke alarms be installed inside every sleep room (even for existing homes) in addition to requiring them outside each sleeping area and on every level of the home. (Additional smoke alarms are required for larger homes.)

How far should a smoke detector be from a vent?

Do not site detectors less than 1m from air supply points or air circulating units. A device should not be mounted within 500mm of any obstruction.

How far should duct detectors be from the unit?

Always choose an appropriate distance from all dampers, bends, and other dimensional changes in the duct system. Preferably, there should be a distance of three times the duct diameter before the source of interference and five times the duct diameter after the source of interference.

Can AC units set off smoke alarms?

The blaring sound of the smoke alarm is always jolting, but if your Air Conditioner is causing your smoke alarm to go off, it is probably not the smoke, but a power surge that is causing this issue. If this is happening, unplug your air conditioner or shut off the circuit powering your AC unit.

How close can a smoke detector be to a furnace?

Combustion particles form when fuel burns. Avoid kitchens, garages, and furnace rooms. Keep units at least 20 feet (6 meters) away from common sources of combustion particles. In small homes, where 20-foot distance is not possible, place the alarm as far away from fuel-burning sources as possible.

Where should smoke detectors be placed NFPA 72?

Install smoke alarms inside and outside every bedroom and sleeping area (like a hallway). Install on every level of the home, including the basement. A smoke alarm should be on the ceiling or high on a wall. Keep smoke alarms away from the kitchen to reduce nuisance, or false, alarms.

What is the code distance for smoke detectors?

The most common application of the Point 7 Rule is smoke detectors in corridor applications. Applying the Point 7 Rule allows spacing between smoke detectors to be extended beyond 30 feet in corridors that are less than 30 feet wide.

Where should smoke detection be located?

Install smoke alarms in all circulation areas/ escape routes and high risk areas. Have at least one smoke alarm in every circulation space on each storey (such as hallways and landings) Position at least one smoke alarm in the principal habitable room (generally the living room)

How many inches should smoke detectors not be installed from a wall?

However, there are specifications as to the location of each smoke alarm on a wall or ceiling: If mounted on the ceiling, it must be more than 4 inches from the wall. It cannot be closer than 4 inches or more than 12 inches from the ceiling if mounted on the wall.

How far should smoke detector be from air intake?

Smoke alarms and smoke detectors shall not be installed within a 36 in. (910 mm) horizontal path from the supply registers of a forced air heating or cooling system and shall be installed outside of the direct airflow from those registers.

How far should a smoke detector be from a range?

Smoke alarms and smoke detectors shall not be installed within an area of exclusion determined by a 10-foot (3.0 m) radial distance along a horizontal flow path from a stationary or fixed cooking appliance, unless listed for installation in close proximity to cooking appliances.

How many smoke alarms do I need in a 3 bedroom house?

According to the United States Department of Homeland Security, and the California Building Code, at least one smoke detector needs to be placed in each of the following areas of your home: On Every Floor Level. In Every Bedroom. In Every Hallway Outside of a Bedroom.

What are three key placement guidelines for the location of smoke detectors?

Install a least one on every level of the home, including the basement. Place a smoke detector in every sleeping area. Ensure a smoke alarm is outside of every room, like in a hallway.

Where should your smoke detector be placed?

Have smoke alarms on every level of your home and in each bedroom and hallway. If you mount alarms on the ceiling, place them 4 inches from the wall. If your alarms are on the wall, they should be 4 to 12 inches from the ceiling. Don't install alarms near windows, vents, or drafty areas.

How far should a smoke detector be from a fan?

Place smoke detectors at least 3 feet from ceiling fans.

Where are the smoke detectors located in HVAC?

According to the NFPA, detectors should be located where air enters or leaves the duct system, and should be “installed in a way as to obtain a representative sample of the airstream.” (17.7. 6.5.

Are smoke detectors connected to AC?

Peripheral devices, like smoke and motion detectors, door, and window sensors can either use AC power to function and require a battery only in case of a loss of power or can function as wireless devices which run independently and on battery power only.

What is the code for ductwork smoke detectors?

NFPA 90A requires the first duct smoke detector to be installed on the supply side of air handler units of more than 2,000 cubic feet per minute (cfm) and requires one on the return side of units of more than 15,000 cfm and serving more than one story.

Previous article
How do you know if a bulb is rotten?
Next article
Why is my dishwasher taking 2 hours?