- Within 3 feet of an air supply vent (supply or air flow) - Within 1 foot of a light fixture. - Within the “dead air space” where the wall meets the ceiling (ceiling smoke alarms must be at least 4” from the wall, wall mounted smoke alarms must be at least 4” and no more than 12” from the ceiling.
Don't install alarms where air movement can delay the alarm. This means they should be away from windows and at least 3 feet from warm or cold air ducts or return ducts. Also, don't install them between an air return and a bedroom door.
17.7. 4, recommends that detectors not be located in the direct airflow or closer than 36 inches from air supply diffuser or return air opening. This recommendation is intended to prevent airflow from diluting smoke or delaying smoke reaching the detector, both of which can significantly delay detection.
Avoid where temperatures are regularly below 40F or above 100F. Avoid near fresh air vents, ceiling fans or very drafty areas (drafts can blow the smoke away from the detector/alarm). Avoid installing closer than 4 inches from the wall or corners.
For many years NFPA 72, National Fire Alarm and Signaling Code, has required as a minimum that smoke alarms be installed inside every sleep room (even for existing homes) in addition to requiring them outside each sleeping area and on every level of the home. (Additional smoke alarms are required for larger homes.)
- Within 3 feet of an air supply vent (supply or air flow) - Within 1 foot of a light fixture. - Within the “dead air space” where the wall meets the ceiling (ceiling smoke alarms must be at least 4” from the wall, wall mounted smoke alarms must be at least 4” and no more than 12” from the ceiling.
Install a least one on every level of the home, including the basement. Place a smoke detector in every sleeping area. Ensure a smoke alarm is outside of every room, like in a hallway.
According to the United States Department of Homeland Security, and the California Building Code, at least one smoke detector needs to be placed in each of the following areas of your home: On Every Floor Level. In Every Bedroom. In Every Hallway Outside of a Bedroom.
Place smoke detectors at least 3 feet from ceiling fans. There are two basic types of smoke detectors: 1. Ionization detectors - Ionization detectors contain radioactive material that ionizes the air, making an electrical path.
Have smoke alarms on every level of your home and in each bedroom and hallway. If you mount alarms on the ceiling, place them 4 inches from the wall. If your alarms are on the wall, they should be 4 to 12 inches from the ceiling. Don't install alarms near windows, vents, or drafty areas.
† Multi-level detection recommended unless risk of stratification is minimal. Do not site detectors less than 1m from air supply points or air circulating units.
Install smoke alarms inside and outside every bedroom and sleeping area (like a hallway). Install on every level of the home, including the basement. A smoke alarm should be on the ceiling or high on a wall. Keep smoke alarms away from the kitchen to reduce nuisance, or false, alarms.
It cannot be closer than 4 inches or more than 12 inches from the ceiling if mounted on the wall. Smoke alarms should not be installed within 36” of windows, exterior doors, or ducts where drafts might interfere with their operation. Smoke alarms should not be painted or have stickers or other decorations present.
The most common application of the Point 7 Rule is smoke detectors in corridor applications. Applying the Point 7 Rule allows spacing between smoke detectors to be extended beyond 30 feet in corridors that are less than 30 feet wide.
907.3. 1Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit where a fire alarm system is required by Section 907.2.
Duct smoke detectors in the return air stream should be located at every return air opening within the smoke compartment, or where the air exits each smoke compartment, or in the duct system before air enters the return air system common to more than one compartment.
The NFPA requires a smoke alarm on every level and outside each sleeping area in existing construction. An existing household with one level and one sleeping area Is required to have one smoke alarm.
To maximize the efficiency of a smoke detector in a bedroom with a ceiling fan, the ideal placement is on the ceiling, away from the fan blades. The smoke detector should be placed at least three feet away from the fan and close to the center of the room.
The best location to install your smoke alarm is in the centre of the ceiling rather than on the wall. During a fire, smoke initially rises and then spreads horizontally. Placing the smoke alarm in the centre of your ceiling means that it is closest to all four points of your room.
The national average cost for installing a smoke detector is between $70 and $150, with most people paying around $112 to install a dual hardwired detector. At the low end of the spectrum, you pay around $44 for a battery-operated ionization detector.
According to the National Fire Protection Association (NFPA), smoke alarms should be installed on every level of your home, including the basement. One fire detector should also be installed inside of every bedroom and outside of each sleeping area.
According to the NFPA, smoke alarms should be placed in every bedroom, outside each sleeping area and on every level of your home. In addition, industry experts recommend having both photoelectric and ionization alarms for optimal protection against flaming and smoldering fires.
All the smoke detectors in your home should be mounted on the ceilings or high on the walls, with no more than 12 inches separating the top of the alarm and the ceiling. If you live in a house with a pitched ceiling, place the smoke detector within three feet of the peak but not within four inches from the top.
Smoke alarms shall be installed not less than 3 feet (914 mm) horizontally from the door or opening of a bathroom that contains a bathtub or shower unless this would prevent placement of a smoke alarm required by this section.